Journal of System Simulation
Abstract
Abstract: Three-phase four-bridge distribution static synchronous compensator (D-STATCOM) has the obvious superiority in solving the problems that brought by the three-phase unbalanced loads in the three-phase four-wire low-voltage power supply system. The Euler-Lagrange (EL) cycle average model is established based on the synchronous rotation d-q-0 coordinates. In the light of the nonlinear and strong coupling characteristics, the passivity-based control (PBC) and inverse cross coupling control strategy using the d-q axis nonlinear decoupling control. PBC controller is designed by energy shaping and damping injection (ESDI) based on the passivity of the system. The closed-loop system is demonstrating asymptotically stable according to the Lyapunov stability theory. Simulation results verify to the control strategy deal with three-phase unbalance and other problems effectively.
Recommended Citation
Hong, Zheng; Xu, Wencheng; and Zhang, Jiawei
(2019)
"Passivity-based Control for Three-phase Four-bridge D-STATCOM in Low-voltage Distribution Network,"
Journal of System Simulation: Vol. 30:
Iss.
3, Article 39.
DOI: 10.16182/j.issn1004731x.joss.201803039
Available at:
https://dc-china-simulation.researchcommons.org/journal/vol30/iss3/39
First Page
1082
DOI Link
https://doi.org/10.16182/j.issn1004731x.joss.201803039
Last Page
1089
CLC
TP391.9
Recommended Citation
Zheng Hong, Xu Wencheng, Zhang Jiawei. Passivity-based Control for Three-phase Four-bridge D-STATCOM in Low-voltage Distribution Network[J]. Journal of System Simulation, 2018, 30(3): 1082-1089.
DOI
10.16182/j.issn1004731x.joss.201803039
Included in
Artificial Intelligence and Robotics Commons, Computer Engineering Commons, Numerical Analysis and Scientific Computing Commons, Operations Research, Systems Engineering and Industrial Engineering Commons, Systems Science Commons